Leak checks and refrigerant reporting for businesses and housing associations

A guide for businesses, property owners and housing associations in Stockholm. Which checks are needed for your refrigeration, freezer or heat pump installation? Here we explain the difference between planned servicing, mandatory leak checks and refrigerant reporting.

When are mandatory leak checks required?

The requirement depends on factors including equipment type, refrigerant and charge quantity. For some F-gases, the quantity is measured in tonnes of carbon dioxide equivalent (CO₂e), while others are assessed by quantity in kilograms. There are exemptions, for example for certain labelled, hermetically sealed equipment. The need for checks therefore has to be assessed for each unit.

Gather the rating plate details, equipment records and latest inspection report. Information about the refrigerant and quantity is a useful starting point for the assessment. Read the Swedish Environmental Protection Agency’s guidance for stationary refrigeration and heat pump equipment.

Is annual servicing the same as a leak check?

No. Servicing may include cleaning, functional checks, fault-finding and preventive maintenance. A statutory leak check is a separate inspection with requirements for how it is carried out and documented. It needs to be explicitly included in the work.

For equipment subject to inspection requirements, the basic interval may be 12, 6 or 3 months, depending on the refrigerant and quantity. A leak detection system can affect the interval. Annual servicing therefore does not automatically mean that all inspection requirements have been met. See the City of Stockholm’s information on inspection intervals.

Refrigerant reporting – when must the annual report be submitted?

The City of Stockholm states that professional operations with reportable installations totalling at least 14 tonnes CO₂e must submit an annual report by 31 March for the preceding calendar year. Which units need to be included must be checked against the rules. Contact the responsible supervisory authority if you are unsure.

The report requires information including the operator, installation, refrigerants and checks carried out. KVT helps with inspection reports and supporting reporting information within the agreed scope. The operator is responsible for ensuring that the report is correct and submitted on time. See the City of Stockholm’s annual reporting instructions.

What do businesses, property owners and housing associations need to do?

This guide is for organisations with refrigeration, freezer or heat pump equipment, such as industry, laboratories, shops and property management businesses. Refrigeration systems in process chillers and climate chambers may also need to be assessed based on refrigerant, quantity and equipment type.

  • Compile a list of the refrigeration and heat pump equipment in the property.
  • Gather details of the refrigerant, charge quantity and previous inspection reports.
  • Clarify who is responsible for operation, planning inspections and any reporting.
  • Plan servicing and statutory checks at the appropriate intervals.

The requirements depend on the installation’s conditions. The equipment and applicable rules determine the need for checks, regardless of whether the operator is a business or a housing association.

Regulations and official sources

Provisions are set out in the EU F-gas Regulation (EU) 2024/573 and Swedish Regulation (2016:1128) on fluorinated greenhouse gases. This is an overview; the assessment of a particular installation is based on current regulations and equipment details.

Last reviewed: 8 November 2026.

Get help assessing your installation’s inspection needs

Contact KVT Stockholm with the property address, manufacturer, model, refrigerant and details of the latest inspection. We help you assess the need and plan suitable work.

Contact KVT about servicing and inspections

Read more about service agreements and refrigeration servicing for businesses and housing associations as well as our services for businesses and industry.